IGS Sustainability
59–61 West Street, Balgowlah
Lit Up — your BASIX & NatHERS report, brought to life
FINAL · CERTIFICATE 1858474M ISSUED 29 JULY 2026
IGS Sustainability
● ISSUED & VALID · CERT 1858474M
NatHERS Climate Zone 56 · Northern Beaches LGA

59–61 West Street, Balgowlah NSW 2093

Residential flat building — 9 apartments (2, 3 & 4-bed) over ground, three upper levels and one basement with 17 resident car spaces. Two ground-floor apartments are affordable units.
BASIX compliance is achieved and the certificate has been issued. Water scored 41 against a target of 40, Energy 62 against 61, and Thermal Comfort passes with all nine dwellings modelled and below their caps. Certificate 1858474M was issued on 29 July 2026 and must be lodged with the development application within three months.
Click a level to explore it
The three scores, and how much room they have
Each BASIX pillar is scored against a target set for this site. Passing is binary — but the margin tells you how much a design change could cost you.
This app displays the figures from the issued certificate and the NatHERS certificate. It does not recompute compliance.
Full report text & tables — Sections 1 to 3

1Executive Summary

IGS has been commissioned to assess the proposed development at 59 West Street, Balgowlah NSW 2093 in terms of BASIX compliance. A BASIX Certificate is a regulatory requirement and demonstrates compliance with the NSW Government's sustainability targets; BASIX assessment and certification has been completed for this project (Certificate No. 1858474M).

With the recommendations provided in the BASIX certificate, the development meets and exceeds the minimum requirements for Water Efficiency, Energy Efficiency and Thermal Comfort, as summarised in Table 1.

Table 1 — BASIX results against targets
RequirementBASIX targetAchievedStatus
Water Efficiency40%41%PASS
Energy Efficiency (GHG)61%62%PASS
Thermal Comfort (overall)PassPassPASS
NatHERS star (min / average)SEPP 2022 — N/A to buildings up to 5 storeysSEPP 2022 — N/A to buildings up to 5 storeysN/A
Max heating / cooling load32.9 / 20.4 MJ/m²·yr32.0 / 18.7 MJ/m²·yrPASS
Max total loadNo cap
Reproduced from the issued report. The "achieved" heating and cooling figures are the highest of any single dwelling (both Unit 03).

2Introduction

BASIX is an NSW State planning policy tool which assesses the environmental performance of new residential premises against a range of water, energy and greenhouse-gas-emissions targets. The assessment has three core components: BASIX Thermal Comfort, BASIX Water and BASIX Energy.

The thermal comfort assessment requires that the thermal performance of dwellings is evaluated and measures put in place to ensure annual heating and cooling loads do not exceed pre-defined limits without compromising the occupant's thermal comfort. This assessment uses computer simulation to evaluate the building fabric thermal performance and passive solar design features such as orientation and solar shading.

The energy section evaluates gas (if any) and electrical energy used for heating, cooling, lighting, ventilation and appliances. The BASIX Energy target is a project-specific minimum percentage reduction in greenhouse-gas emissions relative to the NSW benchmark; for this development the target is 61%.

The water assessment takes account of landscaping and stormwater management as well as the water-efficiency performance of fixtures and fittings such as taps and showers. The BASIX Water target is a required percentage reduction in mains (potable) water use against the fixed benchmark of 90,340 L/person/year; for this development (High Water Target Zone) the target is 40%.

Note: this report is a guide to the BASIX certificate. For the full details of the BASIX requirements, please refer to the BASIX certificate.

3Building Description

This BASIX assessment report is prepared by IGS in support of the proposed development at 59 West Street, Balgowlah NSW 2093, comprising a residential development with one level of basement. The development includes the following space types:

  • 9 residential apartments, comprising a mixture of 2, 3 and 4 bed apartments
  • A residential lobby on ground floor
  • 1 level of basement car parking (17 car parks) dedicated to residents

3.1Site & Location

The site is near St Paul's Catholic College, with West Street on the east, Seaview Street on the west and White Street on the south. The site falls within the Northern Beaches Council local government area, and the Lot / Plan is Lot 13, Section 2, Deposited Plan 2072.

3.2Building Summary

Table 2 — Building summary
Number of buildings1 (Residential Flat Building)
Storeys3 storeys above 1 basement and ground
Total dwellings09 apartments (2, 3 and 4-bed units)
Other building classesN/A
Car parking17 residential carparks in basement 1
Site area1,020 m²
Roof area389 m²
The BASIX certificate describes the same building as "9 dwellings, 4 storeys above ground" — it counts the ground floor as a storey. Both descriptions refer to Ground plus Levels 01, 02 and 03 over one basement.

3.3Information Used in Review

Our review is based on the architectural drawings by PSI Architects, "DA ISSUE ARCHITECTURAL PLANS — 59-61 WEST STREET BALGOWLAH — REV K", dated 22/07/2026.

Table 3 — Architectural drawings list (all Revision K)
SheetDrawing titleRev

Water — the reduction story

Drag the tank to see how the design's water reduction compares to the 40% target, measured against the fixed BASIX benchmark of 90,340 litres per person per year.

Mains-water reduction
The tank shows what's left after the reduction. Drag it, or use the presets.
Fixtures — dwelling vs common area
Switch scope to compare the committed WELS star ratings. Note the taps differ: 5-star inside the apartments, 4-star in common areas.
Where the 41% comes from
There is no rainwater tank and no alternative water supply on this project. The entire reduction is delivered by efficient fixtures and the landscape assumption.
Worth knowing — the landscape numbers are load-bearing
The certificate records 366 m² of common-area lawn, 0 m² of garden and 0 m² of indigenous or low-water-use species. Water scores move when landscape areas move. With no rainwater tank to absorb a change and only a single point of margin (41 against 40), a material change to the landscape design should be checked against the certificate before it is documented.
Full report text & tables — Section 4.1 Water

4.1Water

The water-efficiency performance of the development has been assessed using the online BASIX Tool. The assessment has considered the common-area and central-system features including the landscape design, plant species, water-catchment areas, rainwater-tank size, and the efficiency of the preferred fixtures and fittings in the dwellings.

The development meets the BASIX Water target of 40% — the required percentage reduction in mains (potable) water use against the fixed benchmark of 90,340 litres/person/year — provided the water commitments in Table 5 are installed. For the requirements necessary to achieve this target, refer to BASIX Certificate No. 1858474M.

Table 5 — Water commitments
AreaCommitment
Common-area fixturesCar washing bays: 0 · Showerheads: 4-star (>6 but ≤7.5 L/min) · Toilets: 4-star · Taps: 4-star · Washing machine: no common laundry facility
Central systems1 fire-sprinkler system for the car park · 1 fire-sprinkler system for the building · Fire-sprinkler test water contained within a closed system for re-use: Yes
Private dwellings — fixturesShowerheads: 4-star (>6 but ≤7.5 L/min) · Toilets: 4-star · Kitchen taps: 5-star · Bathroom taps: 5-star
Private dwellings — appliancesWashing machine: 2-star (WELS water) · Dishwasher: 3-star (WELS water)
Pool / spaHot-water recirculation or diversion system: not installed · No pool or spa
Alternative water supplyNo alternative water supply
Reproduced from the issued report and cross-checked against the schedule of commitments in Certificate 1858474M.

Thermal — every dwelling, not a sample

All nine dwellings were modelled individually in FirstRate5. There is no sampling and no extrapolation here — each apartment below has its own NatHERS certificate.

The building, coloured by how close each dwelling runs to its cap
Click any apartment to pin it. Colour is the share of the tightest cap that dwelling uses.
Heating load vs cap
Each dot is one dwelling. The red line is the cap stated in the report.
Apartment detail
Click any apartment — on the building, the chart or the table — to pin it here.
Headroom — how much of each cap is used
Compliance is binary, but headroom is not. These bars show what a design change would eat into.
All nine dwellings
Loads in MJ/m²·yr. Click any row, dot or tile to pin it everywhere. Figures are taken from NatHERS Certificate YNQXNY4LMK and are identical to the thermal-loads table in BASIX Certificate 1858474M.
Design-to targets — what the engineers and the builder need to hit
These are the fabric values the model assumed. They are the numbers to write on the CC drawings and specification.
R-values are minimums — higher complies. U-values and SHGC are maximums — lower complies. These are the estimated minimum BASIX requirements only; they do not address acoustic, fire or safety compliance, which must be met separately.
Full report text & tables — Section 4.3 Thermal Comfort

4.3Thermal Comfort

The energy simulations demonstrating the thermal comfort compliance of the development have been evaluated using FirstRate5 (Version 5.5.5a (3.21)) software, which is approved under the Thermal Comfort protocol of BASIX since March 2021. This computer simulation of residential developments is used to assess the potential of a residential development to have low heating and cooling energy requirements once operational. This method does not guarantee or warrant performance in the practical world, as it considers a simplified and idealised building.

Thermal Comfort targets are set by the Department of Planning in the form of heating and cooling caps. The building's thermal physics is assessed using thermal-performance simulation tools, equating an expected level of heating and cooling energy per dwelling per annum, expressed in MJ per square metre of floor area. Each dwelling has individual heating and cooling caps, and the development has a weighted-average load; the weighted-average caps are harder to achieve than the individual-unit caps.

The "base-case" building fabric and estimated glazing and thermal-performance requirements are described in Table 7. Note these estimated requirements are based on the construction materials nominated by the architect.

The thermal insulation and glazing performance requirements outlined in this report nominate the estimated minimum BASIX requirements only and do not consider requirements for other disciplines such as acoustics, fire or safety compliance.

Compliance with the minimum BASIX requirements does not warrant thermal comfort. All services consultants and contractors shall design and construct the development to comply with the minimum requirements of the NCC Vol 1 & 2 and NSW Section J requirements.

There were several glazing elements for which sufficient information was not available in the drawing package provided. Where this occurred, we modelled the glazing based on our professional judgement and typical industry practice (e.g. assuming awning, sliding, or fixed windows as appropriate). These assumptions have been identified and are included in Appendix D — Insulation and Glazing Markups for your reference.

4.3.1Assessment basis

The assessment covers all 09 dwellings arranged from Ground Level to Level 03. The drawings confirm 4 dwellings at Ground Level, 2 units each on Level 01 and Level 02 and 1 unit on Level 03. The modelling considers orientation, apartment geometry, exposed walls, floor and roof interfaces, glazing, shading, neighbouring obstructions, corridor exposure, ventilation openings and ceiling-fan assumptions.

The heating and cooling caps applied in this assessment are based on the site being in Climate Zone 56 (Mascot / Sydney Airport).

4.3.5Conclusion

All 09 dwellings remain below the applicable individual heating, cooling and total-load caps. The assessment therefore demonstrates a viable pathway for the current design to satisfy the applicable BASIX and NatHERS thermal-performance requirements. Compliance relies on the specifications and assumptions documented in Section 4.3.

Any change to dwelling layouts, glazing performance or operability, shading, exposed construction, insulation, or the surrounding built form must be referred for NatHERS reassessment before certification.

Energy — the all-electric building

62% fewer greenhouse-gas emissions than the NSW benchmark, against a target of 61% — with no gas, no photovoltaics, and a deliberately conservative air-conditioning assumption.

How the building makes its 62%
Click a system to trace it and see where it sits in the building.
The selected system
The 62% reduction
The amber line is the 61% target. The certificate clears it by one point.
What is not in the mix
Commitments by system
Click a system to filter its commitments and highlight where it sits in the building.
    Full report text & tables — Section 4.2 Energy

    4.2Energy

    The energy performance of the development has been assessed using the online BASIX Tool. The assessment has considered common-area and central-system features including lifts, ventilation and lighting for common areas (corridors, lobbies, car park), centralised domestic hot water, and the efficiency of the preferred lighting and appliances in the dwellings.

    The development meets the mandatory BASIX Energy target of 61% provided the energy commitments in Table 6 are installed.

    Table 6 — Energy commitments
    AreaComponentCommitment
    Reproduced from the issued report and cross-checked against the schedule of commitments in Certificate 1858474M.

    Certificate & Next Steps

    The certificate is issued and valid. From here it is about lodging it in time, and carrying its commitments through to construction certificate and occupation.

    Certificate validity
    A BASIX certificate must be submitted with a development application — or lodged with a complying development certificate application — within three months of its date of issue.
    Commitments register — every commitment the certifier will check
    Your live specification tracker. Tick what is confirmed; the pillar meters show how much of each BASIX pillar is specified. This is your tracking — it is not a compliance result.
    Path from here
    Full report text — Disclaimer, Summary & Document Control

    6Summary & Conclusion

    The proposed development has been assessed in terms of its ability to conserve water and minimise energy consumption, and its thermal performance (passive and fabric design) will comply with the BASIX thermal comfort requirements.

    Subject to the provisions of this report, the proposed development is able to meet the BASIX requirements and is BASIX compliant. For further details, please refer to BASIX Certificate No. 1858474M provided.

    5Disclaimer

    This report is prepared using the information described above and inputs from other consultants. Whilst IGS has endeavoured to ensure the information used is accurate, no responsibility or liability to any third party is accepted for any loss or damage arising out of the use of this report by any third party. Any third party wishing to act upon any material contained in this report should first contact IGS for detailed advice which will take into account that party's particular requirements.

    Computer performance assessment provides an estimate of building performance. This estimate is based on a necessarily simplified and idealised version of the building that does not and cannot fully represent all the intricacies of the building once built; as a result, simulation results only represent an interpretation of the potential performance of the building. Although great care has been taken to prepare this report, IGS does not make any representations or give any warranties or assurances as to the accuracy or completeness of the information contained in the report or that the report is free from errors or omissions. IGS and its employees and agents shall not be liable for any loss arising because of any person using or relying on the report, whether caused by error, negligent act or omission.

    Performance of the completed building may be significantly affected by the quality of construction, commissioning, ongoing management of the building, and the way the building is operated, monitored and maintained. Building fabric inputs require verifiable manufacturer data to confirm thermal properties.

    This report is intended as a guide to assist with the application of BASIX. It should be read in conjunction with the BASIX certificate and the NCC applicable to the development; specific applications may vary during the design development of the project.

    Document Control

    RevisionDateIssueAuthorReviewer
    Rev 1.029/07/2026DA IssueSGAA
    Prepared for Galati Design · IGS project EN-N26_203 · © IGS Pty Ltd. All rights reserved.

    Appendices

    • Appendix A — BASIX Certificate 1858474M (17 pages)
    • Appendix B — NatHERS Certificate YNQXNY4LMK (3 pages)
    • Appendix C — Architectural Drawings, PSI Architects Rev K (22 sheets)
    • Appendix D — Insulation & Glazing Mark-ups (6 sheets)

    Every page of every appendix is reproduced in the Evidence room of this app.

    Evidence — the documents

    Every page of the issued report and its four appendices. Click any page to open it full size; use ← → to page through.